N2XFGbY 5 x (1.5-50) mm² 0.6/1 kV

Cu / XLPE / SFWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.9 628
2.5 17.9 667
4 18.7 773
6 20.5 929
10 23.0 1,220
16 26.0 1,614
25 30.0 2,253
35 33.0 2,871
50 37.5 3,626

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 29 33 0.21
2.5 7.41 9.449 0.293 38 43 0.36
4 4.61 5.878 0.275 51 56 0.57
6 3.08 3.927 0.263 64 70 0.86
10 1.83 2.334 0.248 88 93 1.43
16 1.15 1.467 0.238 117 121 2.29
25 0.727 0.927 0.240 157 156 3.58
35 0.524 0.669 0.233 193 187 5.01
50 0.387 0.494 0.232 233 220 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information