N2XRY 3 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / SWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.1 351
2.5 15.1 415
4 16.3 503
6 17.5 603
10 20.5 903
16 23.0 1,161
25 27.0 1,709
35 29.5 2,127
50 31.5 2,424
70 36.5 3,438
95 40.0 4,343
120 43.5 5,172
150 49.5 6,675
185 54.0 7,977
240 60.0 9,995
300 65.0 11,990

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 25 29 0.21
2.5 7.41 9.449 0.293 34 39 0.36
4 4.61 5.878 0.275 44 50 0.57
6 3.08 3.927 0.263 56 63 0.86
10 1.83 2.334 0.248 78 85 1.43
16 1.15 1.467 0.238 103 110 2.29
25 0.727 0.927 0.240 138 142 3.58
35 0.524 0.669 0.233 169 171 5.01
50 0.387 0.494 0.232 209 207 7.15
70 0.268 0.342 0.229 264 253 10.01
95 0.193 0.247 0.224 322 302 13.59
120 0.153 0.196 0.223 372 343 17.16
150 0.124 0.160 0.224 427 383 21.45
185 0.0991 0.128 0.225 490 432 26.46
240 0.0754 0.099 0.223 574 496 34.32
300 0.0601 0.080 0.221 653 554 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information