N2XRY 4 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / SWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.9 395
2.5 16.0 470
4 17.4 575
6 19.5 798
10 22.0 1,058
16 25.5 1,518
25 29.0 2,055
35 32.0 2,585
50 35.5 3,040
70 41.0 4,305
95 45.0 5,476
120 51.5 7,064
150 57.5 8,536
185 61.5 10,189
240 68.0 12,772
300 73.5 15,380

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 28 33 0.21
2.5 7.41 9.449 0.293 37 43 0.36
4 4.61 5.878 0.275 49 55 0.57
6 3.08 3.927 0.263 63 69 0.86
10 1.83 2.334 0.248 86 92 1.43
16 1.15 1.467 0.238 115 120 2.29
25 0.727 0.927 0.240 154 155 3.58
35 0.524 0.669 0.233 189 185 5.01
50 0.387 0.494 0.232 220 212 7.15
70 0.268 0.342 0.229 277 258 10.01
95 0.193 0.247 0.224 339 309 13.59
120 0.153 0.196 0.223 394 350 17.16
150 0.124 0.160 0.224 455 395 21.45
185 0.0991 0.128 0.225 516 442 26.46
240 0.0754 0.099 0.223 605 506 34.32
300 0.0601 0.080 0.221 687 565 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information