N2XRY 5 x (1.5-50) mm2 0.6/1 kV

Cu / XLPE / SWA / PVC
(Copper Conductor, XLPE Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 15.8 441
2.5 17.0 535
4 19.3 768
6 21.0 921
10 23.5 1,235
16 27.0 1,765
25 31.5 2,423
35 34.5 3,057
50 40.0 4,099

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 29 33 0.21
2.5 7.41 9.449 0.293 38 43 0.36
4 4.61 5.878 0.275 51 56 0.57
6 3.08 3.927 0.263 65 70 0.86
10 1.83 2.334 0.248 89 94 1.43
16 1.15 1.467 0.238 119 121 2.29
25 0.727 0.927 0.240 160 157 3.58
35 0.524 0.669 0.233 196 188 5.01
50 0.387 0.494 0.232 238 221 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information