N2XSY 2 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 11.8 188
2.5 12.8 229
4 13.9 285
6 15.0 350
10 16.9 479
16 19.0 643
25 22.5 913
35 24.5 1,171
50 27.5 1,438
70 31.5 1,961
95 35.5 2,621
120 39.0 3,218
150 43.0 3,934
185 48.0 4,887
240 53.5 6,261
300 59.0 7,740

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current
of conductor
at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 29 34 0.21
2.5 7.41 9.449 0.293 38 45 0.36
4 4.61 5.878 0.275 51 59 0.57
6 3.08 3.927 0.263 64 74 0.86
10 1.83 2.334 0.248 88 99 1.43
16 1.15 1.467 0.238 117 129 2.29
25 0.727 0.927 0.240 156 167 3.58
35 0.524 0.669 0.233 192 201 5.01
50 0.387 0.494 0.232 232 238 7.15
70 0.268 0.342 0.229 294 294 10.01
95 0.193 0.247 0.224 359 350 13.59
120 0.153 0.196 0.223 417 399 17.16
150 0.124 0.160 0.224 477 448 21.45
185 0.0991 0.128 0.225 547 504 26.46
240 0.0754 0.099 0.223 647 583 34.32
300 0.0601 0.080 0.221 739 655 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information