N2XSY 3 x (1.5-300) mm² 0.6/1 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 12.3 210
2.5 13.3 261
4 14.5 332
6 15.7 414
10 17.8 581
16 20.5 795
25 23.5 1,146
35 26.0 1,488
50 28.0 1,726
70 32.0 2,411
95 35.5 3,200
120 39.0 3,948
150 43.5 4,866
185 48.5 6,010
240 54.0 7,791
300 59.0 9,587

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current
of conductor
at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 24 29 0.21
2.5 7.41 9.449 0.293 32 38 0.36
4 4.61 5.878 0.275 43 50 0.57
6 3.08 3.927 0.263 54 62 0.86
10 1.83 2.334 0.248 75 84 1.43
16 1.15 1.467 0.238 100 109 2.29
25 0.727 0.927 0.240 132 140 3.58
35 0.524 0.669 0.233 163 169 5.01
50 0.387 0.494 0.232 201 205 7.15
70 0.268 0.342 0.229 254 250 10.01
95 0.193 0.247 0.224 311 300 13.59
120 0.153 0.196 0.223 361 340 17.16
150 0.124 0.160 0.224 414 381 21.45
185 0.0991 0.128 0.225 478 432 26.46
240 0.0754 0.099 0.223 565 499 34.32
300 0.0601 0.080 0.221 648 561 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information