N2XSY 5 x (1.5-50) mm² 0.6/1 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For power plants and switchgear as well as
for installation of sub-station; for installation
indoors in confinned spaces and cable channels
because of small bending radius. As burried
cable, because of its light weight prefered in
where installation is difficult.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 14.0 279
2.5 15.3 355
4 16.8 464
6 18.3 590
10 21.0 851
16 24.0 1,187
25 28.0 1,740
35 31.0 2,284
50 35.5 2,949

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current
of conductor
at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 28 33 0.21
2.5 7.41 9.449 0.293 37 43 0.36
4 4.61 5.878 0.275 49 55 0.57
6 3.08 3.927 0.263 62 69 0.86
10 1.83 2.334 0.248 85 92 1.43
16 1.15 1.467 0.238 113 119 2.29
25 0.727 0.927 0.240 153 155 3.58
35 0.524 0.669 0.233 189 186 5.01
50 0.387 0.494 0.232 229 218 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information