N2XY 3 x (1.5-300) mm2 0.6/1 kV

Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor


Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 12.5 203
2.5 13.5 253
4 14.7 324
6 16.0 405
10 18.0 572
16 20.5 786
25 24.0 1,139
35 26.0 1,483
50 28.0 1,698
70 32.5 2,382
95 36.0 3,168
120 39.0 3,895
150 44.0 4,830
185 48.5 5,971
240 54.5 7,752
300 59.0 9,544

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 21 28 0.21
2.5 7.41 9.449 0.293 32 37 0.36
4 4.61 5.878 0.275 43 49 0.57
6 3.08 3.927 0.263 54 61 0.86
10 1.83 2.334 0.248 74 83 1.43
16 1.15 1.467 0.238 99 107 2.29
25 0.727 0.927 0.240 131 139 3.58
35 0.524 0.669 0.233 162 167 5.01
50 0.387 0.494 0.232 200 203 7.15
70 0.268 0.342 0.229 252 248 10.01
95 0.193 0.247 0.224 309 298 13.59
120 0.153 0.196 0.223 359 339 17.16
150 0.124 0.160 0.224 411 379 21.45
185 0.0991 0.128 0.225 475 430 26.46
240 0.0754 0.099 0.223 562 497 34.32
300 0.0601 0.080 0.221 645 560 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information