N2XY 4 x (1.5-300) mm2 0.6/1 kV

Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

Power cable : Indoors, cable trunking, outdoors
and burried in the ground, for power stations,
industry and switchgear as well as for urban
supply networks, if mechanical damage is
unlikely.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 13.3 232
2.5 14.5 294
4 15.8 382
6 17.2 484
10 19.5 700
16 22.0 973
25 26.0 1,422
35 28.5 1,864
50 32.5 2,218
70 36.5 3,105
95 40.5 4,148
120 45.5 5,180
150 51.5 6,371
185 56.0 7,861
240 62.5 10,208
300 68.0 12,573

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.315 27 31 0.21
2.5 7.41 9.449 0.293 35 41 0.36
4 4.61 5.878 0.275 47 53 0.57
6 3.08 3.927 0.263 59 67 0.86
10 1.83 2.334 0.248 81 89 1.43
16 1.15 1.467 0.238 108 116 2.29
25 0.727 0.927 0.240 146 151 3.58
35 0.524 0.669 0.233 180 181 5.01
50 0.387 0.494 0.232 212 208 7.15
70 0.268 0.342 0.229 265 254 10.01
95 0.193 0.247 0.224 327 305 13.59
120 0.153 0.196 0.223 379 347 17.16
150 0.124 0.160 0.224 442 392 21.45
185 0.0991 0.128 0.225 504 441 26.46
240 0.0754 0.099 0.223 597 511 34.32
300 0.0601 0.080 0.221 685 576 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information