NYKY 2 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 18.8 893
2.5 18.8 916
4 18.8 945
6 19.0 979
10 21.0 1,193
16 23.0 1,448
25 26.0 1,852
35 28.5 2,297
50 32.0 2,889
70 36.0 3,724
95 41.0 4,824
120 44.5 5,746
150 49.0 6,933
185 54.0 8,419
240 60.5 10,689
300 66.5 12,950

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 24 27 0.17
2.5 7.41 8.866 0.315 32 36 0.29
4 4.61 5.516 0.303 42 47 0.46
6 3.08 3.685 0.288 53 60 0.69
10 1.83 2.190 0.269 73 81 1.15
16 1.15 1.376 0.255 96 105 1.84
25 0.727 0.870 0.255 126 135 2.88
35 0.524 0.627 0.246 155 164 4.03
50 0.387 0.464 0.247 186 193 5.75
70 0.268 0.321 0.238 235 238 8.05
95 0.193 0.232 0.238 286 283 10.93
120 0.153 0.184 0.233 332 323 13.80
150 0.124 0.150 0.233 378 362 17.25
185 0.0991 0.121 0.233 431 407 21.28
240 0.0754 0.093 0.232 508 471 27.60
300 0.0601 0.075 0.231 578 528 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information