NYKY 3 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 18.8 916
2.5 18.8 933
4 18.8 966
6 19.8 1,086
10 22.0 1,346
16 24.5 1,659
25 27.5 2,159
35 30.5 2,704
50 33.0 3,095
70 37.0 4,046
95 42.0 5,258
120 45.0 6,256
150 50.0 7,779
185 55.0 9,408
240 61.5 12,050
300 67.5 14,519

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 21 23 0.17
2.5 7.41 8.866 0.315 27 30 0.29
4 4.61 5.516 0.303 36 41 0.46
6 3.08 3.685 0.288 46 51 0.69
10 1.83 2.190 0.269 62 69 1.15
16 1.15 1.376 0.255 82 89 1.84
25 0.727 0.870 0.255 108 115 2.88
35 0.524 0.627 0.246 133 139 4.03
50 0.387 0.464 0.247 167 170 5.75
70 0.268 0.321 0.238 209 208 8.05
95 0.193 0.232 0.238 256 249 10.93
120 0.153 0.184 0.233 296 283 13.80
150 0.124 0.150 0.233 338 317 17.25
185 0.0991 0.121 0.233 390 358 21.28
240 0.0754 0.093 0.232 460 414 27.60
300 0.0601 0.075 0.231 526 465 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information