NYKY 5 x (1.5-50) mm² 0.6/1 kV

Cu / PVC / LS / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 25 sqmm supplied in wooden drum @ 1000 m
35 - 50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 18.8 923
2.5 18.8 966
4 21.5 1,213
6 23.0 1,409
10 25.5 1,790
16 28.5 2,340
25 33.0 3,215
35 36.5 4,054
50 41.5 5,218

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.340 24 28 0.17
2.5 7.41 8.866 0.304 32 36 0.29
4 4.61 5.516 0.303 43 48 0.46
6 3.08 3.685 0.288 54 60 0.69
10 1.83 2.190 0.269 74 79 1.15
16 1.15 1.376 0.255 98 102 1.84
25 0.727 0.870 0.255 131 132 2.88
35 0.524 0.627 0.246 160 158 4.03
50 0.387 0.464 0.247 194 186 5.75

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information