NYKRY 3 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 23.0 1,381
2.5 23.0 1,399
4 23.0 1,432
6 24.5 1,711
10 27.0 2,026
16 29.0 2,411
25 32.5 3,033
35 35.5 3,668
50 39.5 4,401
70 43.5 5,518
95 50.0 7,346
120 53.0 8,504
150 58.5 10,300
185 63.5 12,213
240 70.5 15,214
300 78.0 18,796

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 21 23 0.17
2.5 7.41 8.866 0.315 28 31 0.29
4 4.61 5.516 0.303 37 41 0.46
6 3.08 3.685 0.288 47 51 0.69
10 1.83 2.190 0.269 65 69 1.15
16 1.15 1.376 0.255 85 90 1.84
25 0.727 0.870 0.255 111 115 2.88
35 0.524 0.627 0.246 136 138 4.03
50 0.387 0.464 0.247 172 170 5.75
70 0.268 0.321 0.238 214 207 8.05
95 0.193 0.232 0.238 263 249 10.93
120 0.153 0.184 0.233 303 282 13.80
150 0.124 0.150 0.233 344 316 17.25
185 0.0991 0.121 0.233 394 356 21.28
240 0.0754 0.093 0.232 462 410 27.60
300 0.0601 0.075 0.231 527 459 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information