NYKRY 4 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.


Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 23.0 1,377
2.5 23.0 1,413
4 24.5 1,695
6 26.0 1,896
10 28.5 2,291
16 31.0 2,750
25 35.0 3,617
35 39.0 4,664
50 45.0 5,554
70 50.0 7,299
95 56.5 9,337
120 61.0 10,936
150 67.5 13,116
185 72.5 15,444
240 81.5 20,059
300 88.5 23,907

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.340 24 27 0.17
2.5 7.41 8.866 0.315 32 36 0.29
4 4.61 5.516 0.303 44 47 0.46
6 3.08 3.685 0.288 55 59 0.69
10 1.83 2.190 0.269 74 78 1.15
16 1.15 1.376 0.255 98 101 1.84
25 0.727 0.870 0.255 130 130 2.88
35 0.524 0.627 0.246 159 155 4.03
50 0.387 0.464 0.247 181 175 5.75
70 0.268 0.321 0.238 227 214 8.05
95 0.193 0.232 0.238 279 256 10.93
120 0.153 0.184 0.233 320 290 13.80
150 0.124 0.150 0.233 368 327 17.25
185 0.0991 0.121 0.233 415 365 21.28
240 0.0754 0.093 0.232 490 421 27.60
300 0.0601 0.075 0.231 557 472 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information