NYKBY 2 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC / STA / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 21.0 1,057
2.5 21.0 1,081
4 21.0 1,111
6 21.0 1,146
10 23.0 1,378
16 25.0 1,651
25 28.0 2,083
35 30.5 2,550
50 34.0 3,187
70 38.5 4,077
95 45.0 5,678
120 48.5 6,672
150 53.0 7,953
185 58.5 9,596
240 65.0 12,034
300 71.5 14,464

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 24 27 0.17
2.5 7.41 8.866 0.315 32 35 0.29
4 4.61 5.516 0.303 42 47 0.46
6 3.08 3.685 0.288 54 60 0.69
10 1.83 2.190 0.269 73 80 1.15
16 1.15 1.376 0.255 97 105 1.84
25 0.727 0.870 0.255 127 135 2.88
35 0.524 0.627 0.246 156 162 4.03
50 0.387 0.464 0.247 187 191 5.75
70 0.268 0.321 0.238 235 236 8.05
95 0.193 0.232 0.238 287 280 10.93
120 0.153 0.184 0.233 332 320 13.80
150 0.124 0.150 0.233 377 358 17.25
185 0.0991 0.121 0.233 428 401 21.28
240 0.0754 0.093 0.232 501 461 27.60
300 0.0601 0.075 0.231 567 514 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information