NYKBY 3 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC / STA / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 21.0 1,082
2.5 21.0 1,099
4 21.0 1,132
6 22.0 1,261
10 24.0 1,539
16 26.0 1,873
25 29.5 2,402
35 32.5 2,986
50 35.5 3,417
70 41.0 4,797
95 45.5 6,103
120 49.0 7,208
150 54.5 8,839
185 59.5 10,622
240 66.5 13,440
300 72.5 16,067

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 21 23 0.17
2.5 7.41 8.866 0.315 27 30 0.29
4 4.61 5.516 0.303 36 40 0.46
6 3.08 3.685 0.288 46 51 0.69
10 1.83 2.190 0.269 63 68 1.15
16 1.15 1.376 0.255 83 89 1.84
25 0.727 0.870 0.255 108 114 2.88
35 0.524 0.627 0.246 133 137 4.03
50 0.387 0.464 0.247 166 168 5.75
70 0.268 0.321 0.238 210 206 8.05
95 0.193 0.232 0.238 257 246 10.93
120 0.153 0.184 0.233 296 280 13.80
150 0.124 0.150 0.233 336 312 17.25
185 0.0991 0.121 0.233 385 352 21.28
240 0.0754 0.093 0.232 451 404 27.60
300 0.0601 0.075 0.231 513 452 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information