NYKBY 4 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / LS / PVC / STA / PVC
(Copper Conductor, PVC Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 21.0 1,077
2.5 21.0 1,113
4 22.0 1,246
6 23.5 1,421
10 25.5 1,766
16 28.0 2,175
25 32.0 2,933
35 35.5 3,655
50 42.5 4,827
70 46.0 6,047
95 52.5 7,932
120 57.0 9,433
150 63.5 11,427
185 68.5 13,621
240 76.0 17,132
300 83.0 20,793

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.340 24 27 0.17
2.5 7.41 8.866 0.315 32 35 0.29
4 4.61 5.516 0.303 42 47 0.46
6 3.08 3.685 0.288 53 58 0.69
10 1.83 2.190 0.269 72 77 1.15
16 1.15 1.376 0.255 94 100 1.84
25 0.727 0.870 0.255 126 128 2.88
35 0.524 0.627 0.246 154 153 4.03
50 0.387 0.464 0.247 178 173 5.75
70 0.268 0.321 0.238 222 212 8.05
95 0.193 0.232 0.238 272 254 10.93
120 0.153 0.184 0.233 313 287 13.80
150 0.124 0.150 0.233 360 323 17.25
185 0.0991 0.121 0.233 406 361 21.28
240 0.0754 0.093 0.232 478 415 27.60
300 0.0601 0.075 0.231 542 463 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information