N2XKY 2 x (1.5-300) mm2 0.6/1 kV

Cu / XLPE / LS / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 18.8 885
2.5 18.8 906
4 18.8 935
6 18.8 953
10 19.7 1,081
16 22.0 1,326
25 25.0 1,715
35 27.5 2,063
50 30.0 2,570
70 34.5 3,408
95 38.5 4,376
120 42.5 5,313
150 47.0 6,425
185 52.0 7,847
240 58.0 9,965
300 63.5 12,063

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.340 30 33 0.21
2.5 7.41 9.449 0.315 40 44 0.36
4 4.61 5.878 0.285 53 58 0.57
6 3.08 3.927 0.263 67 73 0.86
10 1.83 2.334 0.248 91 100 1.43
16 1.15 1.467 0.238 121 130 2.29
25 0.727 0.927 0.240 160 167 3.58
35 0.524 0.669 0.233 196 202 5.01
50 0.387 0.494 0.232 237 239 7.15
70 0.268 0.342 0.229 299 294 10.01
95 0.193 0.247 0.224 365 351 13.59
120 0.153 0.196 0.223 423 399 17.16
150 0.124 0.160 0.224 484 448 21.45
185 0.0991 0.128 0.225 554 504 26.46
240 0.0754 0.099 0.223 655 584 34.32
300 0.0601 0.080 0.221 747 656 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information