N2XKY 5 x (1.5-50) mm2 0.6/1 kV

Cu / XLPE / LS / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 18.8 911
2.5 18.8 953
4 19.5 1,059
6 21.5 1,245
10 24.0 1,608
16 26.5 2,053
25 31.0 2,862
35 34.5 3,659
50 39.0 4,698

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 29 32 0.21
2.5 7.41 9.449 0.293 38 42 0.36
4 4.61 5.878 0.275 51 56 0.57
6 3.08 3.927 0.263 64 69 0.86
10 1.83 2.334 0.248 88 93 1.43
16 1.15 1.467 0.238 117 120 2.29
25 0.727 0.927 0.240 157 155 3.58
35 0.524 0.669 0.233 193 186 5.01
50 0.387 0.494 0.232 233 218 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information