N2XKRY 4 x (1.5-300) mm2 0.6/1 kV

Cu / XLPE / LS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor

Standard Packing
1.5 - 25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 23.0 1,374
2.5 23.0 1,390
4 23.0 1,436
6 24.0 1,583
10 27.0 2,100
16 29.5 2,544
25 33.5 3,347
35 37.5 4,243
50 41.5 5,039
70 46.5 6,440
95 52.5 8,445
120 57.5 10,124
150 64.0 12,172
185 69.0 14,480
240 76.0 18,069
300 83.5 22,246

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 29 31 0.21
2.5 7.41 9.449 0.304 39 42 0.36
4 4.61 5.878 0.275 51 54 0.57
6 3.08 3.927 0.263 65 68 0.86
10 1.83 2.334 0.248 89 92 1.43
16 1.15 1.467 0.238 117 118 2.29
25 0.727 0.927 0.240 156 153 3.58
35 0.524 0.669 0.233 192 183 5.01
50 0.387 0.494 0.232 224 210 7.15
70 0.268 0.342 0.229 278 256 10.01
95 0.193 0.247 0.224 343 308 13.59
120 0.153 0.196 0.223 395 348 17.16
150 0.124 0.160 0.224 456 393 21.45
185 0.0991 0.128 0.225 518 441 26.46
240 0.0754 0.099 0.223 608 508 34.32
300 0.0601 0.080 0.221 694 569 42.90

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information