N2XKRY 5 x (1.5-50) mm2 0.6/1 kV

Cu / XLPE / LS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 25 sqmm supplied in wooden drum @ 1000 m
35 - 50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 23.0 1,376
2.5 23.0 1,419
4 23.5 1,546
6 26.0 1,906
10 28.5 2,342
16 31.5 2,877
25 36.0 3,845
35 40.5 5,048
50 45.0 6,238

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 30 32 0.21
2.5 7.41 9.449 0.293 40 42 0.36
4 4.61 5.878 0.275 53 56 0.57
6 3.08 3.927 0.263 67 70 0.86
10 1.83 2.334 0.248 92 93 1.43
16 1.15 1.467 0.238 121 120 2.29
25 0.727 0.927 0.240 161 155 3.58
35 0.524 0.669 0.233 198 185 5.01
50 0.387 0.494 0.232 238 217 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information