N2XKBY 5 x (1.5-50) mm² 0.6/1 kV

Cu / XLPE / LS / PVC / DSTA / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 35 sqmm supplied in wooden drum @ 1000 m
50 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 21.0 1,076
2.5 21.0 1,119
4 21.5 1,230
6 23.0 1,430
10 25.5 1,817
16 28.5 2,288
25 33.0 3,150
35 37.0 3,996
50 42.5 5,470

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 15.429 0.328 30 32 0.21
2.5 7.41 9.449 0.293 39 42 0.36
4 4.61 5.878 0.275 51 55 0.57
6 3.08 3.927 0.263 65 69 0.86
10 1.83 2.334 0.248 88 92 1.43
16 1.15 1.467 0.238 117 119 2.29
25 0.727 0.927 0.240 157 153 3.58
35 0.524 0.669 0.233 192 183 5.01
50 0.387 0.494 0.232 232 215 7.15

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information