RE2YRY (2-50) Pairs x 1.5 mm² & (2-50) Pairs x 2.5 mm² 300/500 V

CU / PE / IS / PVC / SWA / PVC
(Copper Conductor, PE Insulated, Individual Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : BS 5308-1 & IEC 60502

Application

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid (re) or non compacted circular stranded (rm)

Standard Packing
Size 1.5 mm² :
2 - 20 pairs supplied in wooden drum @ 1000 m
24 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
2 - 19 pairs supplied in wooden drum @ 1000 m
20 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

Construction Data

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
2 18.9 678 20.5 807
3 21.0 870 21.5 889
4 22.5 965 24.0 1,127
5 23.5 1,016 25.5 1,194
6 27.0 1,242 28.5 1,423
7 27.0 1,256 28.5 1,444
9 30.5 1,508 35.0 2,065
10 32.0 1,629 36.5 2,214
12 36.0 2,115 40.0 2,518
14 37.0 2,253 41.0 2,729
15 38.5 2,396 43.5 2,952
16 40.5 2,541 45.0 3,103
18 42.0 2,725 49.0 3,762
19 42.0 2,771 49.0 3,831
20 44.0 2,970 51.5 4,110
24 52.5 3,993 59.5 4,876
30 55.0 4,402 62.5 5,538
36 59.5 5,102 67.5 6,329
40 61.5 5,410 70.0 6,765
48 67.0 6,152 78.5 8,661
50 68.5 6,313 80.0 8,896

Electrical Data

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
max.
min. max. -
mm2 ohm/km G.ohm.km pF/m volt/1 min
1.5 12.3 5 120 1000
2.5 7.56 5 120 1000