RE2YY (2-50) Pairs x 1.5 mm2 & (2-50) Pairs x 2.5 mm2 300/500 V

CU / PE
/ IS / PVC
(Copper Conductor, PE Insulated, Individual Screen, PVC Sheathed)
Standard Specification : BS 5308-1 & IEC 60502

Application

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid or non compacted circular stranded

Standard Packing
Size 1.5 mm² :
2 - 36 pairs supplied in wooden drum @ 1000 m
40 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
2 - 20 pairs supplied in wooden drum @ 1000 m
24 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

Construction Data

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
2 12.6 244 15.4 362
3 13.6 287 16.4 419
4 14.9 339 17.9 496
5 16.3 345 19.6 506
6 19.1 442 23.0 624
7 19.1 457 23.0 646
9 23.0 576 27.5 830
10 24.5 633 29.5 927
12 27.5 767 32.5 1,092
14 28.5 869 34.0 1,258
15 30.0 946 36.0 1,370
16 31.5 1,008 38.0 1,459
18 33.5 1,095 40.0 1,606
19 33.5 1,141 40.0 1,675
20 35.0 1,271 42.5 1,886
24 41.5 1,492 50.0 2,168
30 44.0 1,792 53.5 2,640
36 48.5 2,161 58.0 3,158
40 50.0 2,366 61.0 3,490
48 55.5 2,795 68.0 4,189
50 57.0 2,900 69.5 4,347

Electrical Data

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
max.
min. max. -
mm2 ohm/km G.ohm.km pF/m volt/1 min
1.5 12.3 5 120 1000
2.5 7.56 5 120 1000