REYKRY (2-50) Pairs x 1.5 mm² & (2-50) Pairs x 2.5 mm² 300/500 V

CU / PVC
/ IS / PVC / LS / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Individual Screen, Lead Sheathed, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : BS 5308-2 & IEC 60502

Application

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid (re) or non compacted circular stranded (rm)

Standard Packing
Size 1.5 mm² :
2 - 20 pairs supplied in wooden drum @ 1000 m
24 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
2 - 12 pairs supplied in wooden drum @ 1000 m
14 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

Construction Data

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
2 23.5 1,519 26.0 1,856
3 24.0 1,616 27.0 2,003
4 25.5 1,770 29.5 2,306
5 27.0 1,885 31.5 2,479
6 29.5 2,186 35.5 3,211
7 29.5 2,205 35.5 3,238
9 34.5 3,053 42.0 4,247
10 36.5 3,258 44.0 4,575
12 39.0 3,604 48.5 5,445
14 40.5 3,952 50.5 5,968
15 42.5 4,285 53.0 6,532
16 44.0 4,491 55.0 6,851
18 48.0 5,305 58.0 7,383
19 48.0 5,355 58.0 7,462
20 49.5 5,688 61.0 8,185
24 56.5 6,775 69.5 9,745
30 59.5 7,694 73.5 11,038
36 64.0 8,729 80.5 13,635
40 66.5 9,390 83.5 14,376
48 73.0 10,946 91.5 16,802
50 75.5 12,082 93.0 17,274

Electrical Data

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
max.
min. max. -
mm2 ohm/km M.ohm.km pF/m volt/1 min
1.5 12.3 1 250 1000
2.5 7.56 1 250 1000