REYRY (2-50) Pairs x 1.5 mm² & (2-50) Pairs x 2.5 mm² 300/500 V

CU
/ PVC / IS / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Individual Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : BS 5308-2 & IEC 60502

Application

Instrumentation cables are suitable for
industrial control system as needed in
measurement, control, signalling and
data system technology.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
All construction supplied in solid (re) or non compacted circular stranded (rm)

Standard Packing
Size 1.5 mm² :
2 - 20 pairs supplied in wooden drum @ 1000 m
24 - 50 pairs supplied in wooden drum on available length
Size 2.5 mm² :
2 - 16 pairs supplied in wooden drum @ 1000 m
18 - 50 pairs supplied in wooden drum on available length
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

Construction Data

No.
of
pairs
Size
1.5 mm2
2.5 mm2
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
2 18.9 687 21.5 869
3 21.0 884 23.0 1,077
4 22.5 984 24.5 1,222
5 23.5 1,039 26.5 1,294
6 27.0 1,269 30.0 1,536
7 27.0 1,289 30.0 1,563
9 30.5 1,549 36.0 2,203
10 32.0 1,675 38.5 2,407
12 36.0 2,170 41.5 2,717
14 37.0 2,317 43.0 2,969
15 38.5 2,464 45.5 3,206
16 40.5 2,610 48.5 3,770
18 42.0 2,808 51.5 4,124
19 42.0 2,858 51.5 4,204
20 44.0 3,061 54.0 4,583
24 52.5 4,103 62.0 5,291
30 55.0 4,540 66.0 6,103
36 59.5 5,267 71.0 6,913
40 61.5 5,594 73.5 7,435
48 67.0 6,372 82.5 9,460
50 68.5 6,543 84.0 9,718

Electrical Data

Conductor Insulation Mutual
Capacitance
AC
Voltage
Test
Nominal
Cross
Section
Resistance
at 20°C
Resistance
at 20°C
max.
min. max. -
mm2 ohm/km M.ohm.km pF/m volt/1 min
1.5 12.3 1 250 1000
2.5 7.56 1 250 1000