NA2XSY 1 x (35-800) mm² 12/20 kV

Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For power stations and switchgear as well
as stations because of small bending radius
in confined spaces indoors. As underground
because of light weight where installation
conditions are diffcult.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
35 - 800 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 800 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 24.5 669
50 25.5 698
70 27.5 824
95 29.0 948
120 30.5 1,074
150 32.0 1,185
185 34.0 1,300
240 36.5 1,535
300 38.5 1,759
400 42.0 2,107
500 45.0 2,506
630 49.5 3,063
800 52.7 3,713

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.434 0.480 154 141 158 144 3.29 1.14
50 0.641 0.822 0.415 0.461 184 166 188 170 4.70 1.14
70 0.443 0.568 0.390 0.437 230 204 236 209 6.58 1.14
95 0.320 0.411 0.372 0.418 280 244 287 249 8.93 1.14
120 0.253 0.325 0.360 0.407 324 277 332 284 11.28 1.14
150 0.206 0.265 0.350 0.396 367 310 376 318 14.10 1.14
185 0.164 0.211 0.337 0.384 422 352 433 360 17.39 1.14
240 0.125 0.161 0.326 0.372 499 408 512 418 22.56 1.14
300 0.100 0.130 0.316 0.363 572 461 587 472 28.20 1.14
400 0.0778 0.102 0.304 0.350 674 530 692 542 37.60 1.14
500 0.0605 0.080 0.296 0.342 782 604 802 618 47.00 1.14
630 0.0469 0.064 0.285 0.331 921 692 945 708 59.22 1.14
800 0.0367 0.051 0.277 0.324 1031 780 1071 787 75.20 1.14

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information