NA2XSY 1 x (25-800) mm² 8.7/15 kV

Al / XLPE/ CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For power stations and switchgear as well
as stations because of small bending radius
in confined spaces indoors. As underground
because of light weight where installation
conditions are diffcult.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 800 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 800 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 21.0 520
35 22.5 584
50 23.5 651
70 25.0 722
95 27.0 853
120 28.5 961
150 30.0 1,081
185 32.0 1,231
240 34.0 1,406
300 36.5 1,640
400 40.0 1,977
500 42.5 2,368
630 47.5 2,910
800 50.5 3,523

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.442 0.488 125 118 128 120 2.35 1.14
35 0.868 1.113 0.416 0.463 152 141 156 144 3.29 1.14
50 0.641 0.822 0.399 0.445 182 166 186 170 4.70 1.14
70 0.443 0.568 0.373 0.419 228 204 234 209 6.58 1.14
95 0.320 0.411 0.357 0.404 277 244 285 250 8.93 1.14
120 0.253 0.325 0.345 0.391 321 277 329 284 11.28 1.14
150 0.206 0.265 0.336 0.383 364 310 373 318 14.10 1.14
185 0.164 0.211 0.325 0.371 420 352 431 361 17.39 1.14
240 0.125 0.161 0.313 0.360 496 408 509 418 22.56 1.14
300 0.100 0.130 0.305 0.352 569 461 584 472 28.20 1.14
400 0.0778 0.102 0.294 0.340 671 530 689 542 37.60 1.14
500 0.0605 0.080 0.287 0.333 779 603 800 618 47.00 1.14
630 0.0469 0.064 0.276 0.322 919 691 943 707 59.22 1.14
800 0.0367 0.052 0.269 0.315 1029 780 1071 787 75.20 1.14

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information