NA2XSEY 3 x (25-300) mm² 8.7/15 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 46.5 2,097
35 49.5 2,384
50 52.0 2,673
70 56.5 3,207
95 60.0 3,719
120 63.5 4,194
150 66.5 4,662
185 71.5 5,384
240 76.5 6,321
300 81.5 7,277

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.400 119 112 2.35 1.03
35 0.868 1.113 0.376 144 134 3.29 1.03
50 0.641 0.822 0.361 171 158 4.70 1.03
70 0.443 0.568 0.338 213 193 6.58 1.03
95 0.320 0.411 0.323 258 231 8.93 1.03
120 0.253 0.325 0.312 297 262 11.28 1.03
150 0.206 0.265 0.304 335 293 14.10 1.37
185 0.164 0.211 0.294 383 332 17.39 1.37
240 0.125 0.162 0.284 449 384 22.56 1.37
300 0.100 0.130 0.276 512 432 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information