NA2XSEY 3 x (25-300) mm2 3.6/6 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 36.5 1,380
35 39.5 1,620
50 42.0 1,908
70 46.5 2,322
95 50.0 2,781
120 54.0 3,252
150 57.0 3,673
185 61.5 4,268
240 67.0 5,172
300 73.0 6,226

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.346 115 112 2.35 1.03
35 0.868 1.113 0.326 140 134 3.29 1.03
50 0.641 0.822 0.314 166 158 4.70 1.03
70 0.443 0.568 0.296 208 193 6.58 1.03
95 0.320 0.411 0.284 253 231 8.93 1.03
120 0.253 0.325 0.276 291 262 11.28 1.03
150 0.206 0.265 0.269 329 293 14.10 1.03
185 0.164 0.212 0.262 379 333 17.39 1.03
240 0.125 0.162 0.256 446 385 22.56 1.37
300 0.100 0.130 0.253 508 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information