NA2XSEFGbY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 56.5 3,964
50 59.0 4,302
70 63.0 4,938
95 67.0 5,555
120 70.0 6,148
150 73.5 6,771
185 78.0 7,587
240 83.0 8,627
300 88.0 9,730

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 147 135 3.29 1.03
50 0.641 0.822 0.380 175 159 4.70 1.03
70 0.443 0.568 0.357 218 194 6.58 1.03
95 0.320 0.411 0.340 263 232 8.93 1.37
120 0.253 0.325 0.328 302 263 11.28 1.37
150 0.206 0.265 0.319 339 293 14.10 1.37
185 0.164 0.211 0.308 388 332 17.39 1.37
240 0.125 0.162 0.297 453 383 22.56 1.37
300 0.100 0.130 0.289 515 430 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information