NA2XSEBY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC / STA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 56.0 3,659
50 58.5 3,998
70 63.0 4,581
95 66.5 5,186
120 70.0 5,737
150 73.5 6,346
185 77.5 7,094
240 84.0 8,941
300 89.0 10,064

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 147 135 3.29 1.03
50 0.641 0.822 0.380 175 159 4.70 1.03
70 0.443 0.568 0.357 218 194 6.58 1.03
95 0.320 0.411 0.340 263 232 8.93 1.37
120 0.253 0.325 0.328 302 263 11.28 1.37
150 0.206 0.265 0.319 339 294 14.10 1.37
185 0.164 0.211 0.308 389 333 17.39 1.37
240 0.125 0.162 0.297 454 383 22.56 1.37
300 0.100 0.130 0.289 516 430 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information