NA2XSEBY 3 x (25-300) mm² 8.7/15 kV

Al / XLPE / CTS / PVC / STA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 48.0 2,792
35 51.0 3,122
50 53.5 3,448
70 58.0 4,054
95 62.0 4,624
120 65.0 5,151
150 68.5 5,666
185 73.0 6,460
240 78.0 7,474
300 84.0 9,262

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.400 121 113 2.35 1.03
35 0.868 1.113 0.376 146 135 3.29 1.03
50 0.641 0.822 0.361 174 159 4.70 1.03
70 0.443 0.568 0.338 216 194 6.58 1.03
95 0.320 0.411 0.323 261 232 8.93 1.03
120 0.253 0.325 0.312 300 264 11.28 1.03
150 0.206 0.265 0.304 338 294 14.10 1.37
185 0.164 0.211 0.294 387 333 17.39 1.37
240 0.125 0.162 0.284 452 384 22.56 1.37
300 0.100 0.130 0.276 515 431 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information