NA2XSEBY 3 x (25-300) mm² 3.6/6 kV

Al / XLPE / CTS / PVC / STA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 38.0 1,922
35 41.0 2,206
50 43.5 2,517
70 48.0 3,016
95 52.0 3,534
120 55.5 4,062
150 59.0 4,531
185 63.0 5,191
240 68.5 6,180
300 75.0 7,327

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.346 117 113 2.35 1.03
35 0.868 1.113 0.326 142 136 3.29 1.03
50 0.641 0.822 0.314 170 159 4.70 1.03
70 0.443 0.568 0.296 212 195 6.58 1.03
95 0.320 0.411 0.284 257 233 8.93 1.03
120 0.253 0.325 0.276 295 264 11.28 1.03
150 0.206 0.265 0.269 334 295 14.10 1.03
185 0.164 0.212 0.262 384 334 17.39 1.03
240 0.125 0.162 0.256 450 386 22.56 1.37
300 0.100 0.130 0.253 512 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information