NA2XSEBY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / STA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 42.5 2,270
35 45.5 2,619
50 48.0 2,918
70 52.5 3,431
95 56.5 4,030
120 60.0 4,520
150 63.0 5,018
185 67.5 5,697
240 73.0 6,733
300 77.5 7,697

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 119 113 2.35 1.03
35 0.868 1.113 0.350 144 135 3.29 1.03
50 0.641 0.822 0.336 172 159 4.70 1.03
70 0.443 0.568 0.316 214 195 6.58 1.03
95 0.320 0.411 0.303 259 232 8.93 1.03
120 0.253 0.325 0.293 298 264 11.28 1.03
150 0.206 0.265 0.285 336 295 14.10 1.03
185 0.164 0.211 0.277 386 334 17.39 1.37
240 0.125 0.162 0.268 451 385 22.56 1.37
300 0.100 0.130 0.261 514 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information