NA2XSEFGbY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 42.5 2,492
35 46.0 2,857
50 48.5 3,182
70 52.5 3,700
95 57.0 4,329
120 60.0 4,856
150 63.0 5,372
185 67.5 6,084
240 73.0 7,140
300 78.0 8,166

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 119 113 2.35 1.03
35 0.868 1.113 0.350 144 135 3.29 1.03
50 0.641 0.822 0.336 172 159 4.70 1.03
70 0.443 0.568 0.316 214 195 6.58 1.03
95 0.320 0.411 0.303 259 232 8.93 1.03
120 0.253 0.325 0.293 298 264 11.28 1.03
150 0.206 0.265 0.285 336 295 14.10 1.03
185 0.164 0.211 0.277 386 334 17.39 1.37
240 0.125 0.162 0.268 450 384 22.56 1.37
300 0.100 0.130 0.261 512 431 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information