NA2XSEFGbY 3 x (25-300) mm² 8.7/15 kV

Al / XLPE / CTS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 48.5 3,056
35 51.0 3,380
50 53.5 3,732
70 58.5 4,364
95 62.0 4,966
120 65.5 5,535
150 68.5 6,042
185 73.0 6,891
240 78.5 7,929
300 83.0 8,947

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.400 121 113 2.35 1.03
35 0.868 1.113 0.376 146 135 3.29 1.03
50 0.641 0.822 0.361 174 159 4.70 1.03
70 0.443 0.568 0.338 216 194 6.58 1.03
95 0.320 0.411 0.323 261 232 8.93 1.03
120 0.253 0.325 0.312 300 263 11.28 1.03
150 0.206 0.265 0.304 338 294 14.10 1.37
185 0.164 0.211 0.294 386 332 17.39 1.37
240 0.125 0.162 0.284 452 383 22.56 1.37
300 0.100 0.130 0.276 514 431 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information