NA2XSERY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 46.5 3,417
35 49.5 3,840
50 52.0 4,225
70 56.5 4,837
95 60.5 5,535
120 64.0 6,139
150 67.0 6,712
185 71.0 7,490
240 78.0 9,474
300 83.0 10,662

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 122 114 2.35 1.03
35 0.868 1.113 0.350 147 136 3.29 1.03
50 0.641 0.822 0.336 175 160 4.70 1.03
70 0.443 0.568 0.316 219 197 6.58 1.03
95 0.320 0.411 0.303 263 234 8.93 1.03
120 0.253 0.325 0.293 303 266 11.28 1.03
150 0.206 0.265 0.285 342 297 14.10 1.03
185 0.164 0.211 0.277 392 336 17.39 1.37
240 0.125 0.162 0.268 459 387 22.56 1.37
300 0.100 0.130 0.261 521 435 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information