NA2XSERY 3 x (25-300) mm² 8.7/15 kV

Al / XLPE / CTS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 52.0 4,099
35 55.0 4,509
50 57.5 4,882
70 62.0 5,620
95 66.0 6,296
120 69.0 6,895
150 72.5 7,486
185 78.5 9,262
240 83.5 10,461
300 88.5 11,679

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.400 123 114 2.35 1.03
35 0.868 1.113 0.376 149 136 3.29 1.03
50 0.641 0.822 0.361 177 160 4.70 1.03
70 0.443 0.568 0.338 219 196 6.58 1.03
95 0.320 0.411 0.323 265 233 8.93 1.03
120 0.253 0.325 0.312 304 265 11.28 1.03
150 0.206 0.265 0.304 343 296 14.10 1.37
185 0.164 0.211 0.294 393 335 17.39 1.37
240 0.125 0.162 0.284 460 387 22.56 1.37
300 0.100 0.130 0.276 522 434 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information