NA2XSERY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC / SWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 60.0 5,172
50 62.5 5,557
70 66.5 6,279
95 70.5 6,990
120 74.0 7,614
150 79.0 9,176
185 83.0 10,120
240 88.5 11,358
300 93.0 12,519

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 150 136 3.29 1.03
50 0.641 0.822 0.380 178 160 4.70 1.03
70 0.443 0.568 0.357 221 196 6.58 1.03
95 0.320 0.411 0.340 267 233 8.93 1.37
120 0.253 0.325 0.328 306 265 11.28 1.37
150 0.206 0.265 0.319 344 295 14.10 1.37
185 0.164 0.211 0.308 394 334 17.39 1.37
240 0.125 0.162 0.297 460 386 22.56 1.37
300 0.100 0.130 0.289 522 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information