NA2XSEY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 40.5 1,663
35 44.0 1,962
50 46.5 2,224
70 50.5 2,672
95 55.0 3,230
120 58.5 3,671
150 61.5 4,122
185 66.0 4,738
240 71.0 5,661
300 76.0 6,586

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 117 112 2.35 1.03
35 0.868 1.113 0.350 142 134 3.29 1.03
50 0.641 0.822 0.336 169 158 4.70 1.03
70 0.443 0.568 0.316 211 194 6.58 1.03
95 0.320 0.411 0.303 255 230 8.93 1.03
120 0.253 0.325 0.293 294 262 11.28 1.03
150 0.206 0.265 0.285 332 293 14.10 1.03
185 0.164 0.211 0.277 381 332 17.39 1.37
240 0.125 0.162 0.268 447 384 22.56 1.37
300 0.100 0.130 0.261 510 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information