NA2XSEY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 54.5 2,842
50 57.0 3,144
70 61.0 3,661
95 65.0 4,238
120 68.5 4,739
150 72.0 5,296
185 76.5 5,980
240 81.5 6,956
300 86.0 7,922

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 145 134 3.29 1.03
50 0.641 0.822 0.380 173 158 4.70 1.03
70 0.443 0.568 0.357 215 193 6.58 1.03
95 0.320 0.411 0.340 260 230 8.93 1.37
120 0.253 0.325 0.328 298 262 11.28 1.37
150 0.206 0.265 0.319 336 292 14.10 1.37
185 0.164 0.211 0.308 385 332 17.39 1.37
240 0.125 0.162 0.297 451 384 22.56 1.37
300 0.100 0.130 0.289 514 432 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information