NA2XSR(AL)Y 1 x (25-630) mm² 6/10 kV

Al / XLPE/ CTS / PVC / AWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 500 sqmm supplied in wooden drum @ 1000 m
630 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 24.5 752
35 26.0 830
50 27.0 911
70 29.0 1,056
95 30.5 1,159
120 32.0 1,295
150 34.5 1,518
185 36.5 1,729
240 39.0 1,996
300 41.0 2,204
400 44.5 2,599
500 49.5 3,239
630 54.0 3,875

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.472 0.518 130 119 133 122 2.35 1.14
35 0.868 1.113 0.445 0.491 158 142 162 145 3.29 1.14
50 0.641 0.822 0.426 0.473 189 168 193 171 4.70 1.14
70 0.443 0.568 0.401 0.447 236 205 241 209 6.58 1.14
95 0.320 0.411 0.381 0.427 285 244 291 249 8.93 1.14
120 0.253 0.325 0.369 0.415 328 277 334 282 11.28 1.14
150 0.206 0.265 0.364 0.410 372 308 378 313 14.10 1.14
185 0.164 0.211 0.353 0.399 426 347 432 351 17.39 1.14
240 0.125 0.161 0.341 0.387 497 398 503 401 22.56 1.14
300 0.100 0.130 0.330 0.377 564 445 569 446 28.20 1.14
400 0.0778 0.102 0.317 0.363 654 503 656 502 37.60 1.14
500 0.0605 0.080 0.316 0.362 740 554 737 547 47.00 1.14
630 0.0469 0.063 0.302 0.348 849 617 839 605 59.22 1.14

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information