NA2XSEKBY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / LS / PVC / DSTA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 48.5 5,033
35 52.0 5,606
50 54.5 6,263
70 59.5 7,292
95 63.5 8,404
120 67.5 9,436
150 71.0 10,440
185 75.5 11,738
240 81.5 13,569
300 88.5 16,438

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 120 112 2.35 1.03
35 0.868 1.113 0.350 145 134 3.29 1.03
50 0.641 0.822 0.336 172 157 4.70 1.03
70 0.443 0.568 0.316 214 19 6.58 1.03
95 0.320 0.411 0.303 258 229 8.93 1.03
120 0.253 0.325 0.293 296 260 11.28 1.03
150 0.206 0.265 0.285 333 290 14.10 1.03
185 0.164 0.211 0.277 382 328 17.39 1.37
240 0.125 0.162 0.268 444 377 22.56 1.37
300 0.100 0.130 0.261 503 421 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information