NA2XSEKFGbY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 48.5 5,293
35 52.0 5,881
50 55.0 6,559
70 59.5 7,613
95 64.0 8,806
120 68.0 9,820
150 71.5 10,839
185 76.0 12,166
240 82.0 14,038
300 87.5 16,090

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 120 112 2.35 1.03
35 0.868 1.113 0.350 145 134 3.29 1.03
50 0.641 0.822 0.336 172 157 4.70 1.03
70 0.443 0.568 0.316 214 193 6.58 1.03
95 0.320 0.411 0.303 258 229 8.93 1.03
120 0.253 0.325 0.293 296 260 11.28 1.03
150 0.206 0.265 0.285 333 290 14.10 1.03
185 0.164 0.211 0.277 381 328 17.39 1.37
240 0.125 0.162 0.268 443 376 22.56 1.37
300 0.100 0.130 0.261 502 421 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information