NA2XSEKFGbY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 63.5 8,347
50 66.5 9,167
70 71.0 10,388
95 75.0 11,593
120 79.0 12,740
150 83.0 14,017
185 87.5 15,541
240 93.0 17,430
300 98.0 19,397

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 147 133 3.29 1.03
50 0.641 0.822 0.380 174 157 4.70 1.03
70 0.443 0.568 0.357 216 192 6.58 1.03
95 0.320 0.411 0.340 261 229 8.93 1.37
120 0.253 0.325 0.328 299 259 11.28 1.37
150 0.206 0.265 0.319 335 289 14.10 1.37
185 0.164 0.211 0.308 382 326 17.39 1.37
240 0.125 0.162 0.297 445 375 22.56 1.37
300 0.100 0.130 0.289 503 419 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information