NA2XSEKY 3 x (25-300) mm² 6/10 kV

Al / XLPE / CTS / PVC / LS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 44.5 4,107
35 47.5 4,591
50 50.5 5,166
70 55.0 6,095
95 59.5 7,113
120 63.0 8,006
150 66.0 8,902
185 70.5 10,099
240 76.5 11,762
300 82.0 13,631

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.372 120 113 2.35 1.03
35 0.868 1.113 0.350 145 135 3.29 1.03
50 0.641 0.822 0.336 173 159 4.70 1.03
70 0.443 0.568 0.316 215 195 6.58 1.03
95 0.320 0.411 0.303 260 232 8.93 1.03
120 0.253 0.325 0.293 299 264 11.28 1.03
150 0.206 0.265 0.285 338 295 14.10 1.03
185 0.164 0.211 0.277 388 335 17.39 1.37
240 0.125 0.162 0.268 454 386 22.56 1.37
300 0.100 0.130 0.261 517 434 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information