NA2XSEKY 3 x (35-300) mm² 12/20 kV

Al / XLPE / CTS / PVC / LS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 59.0 6,715
50 61.5 7,395
70 66.0 8,454
95 70.0 9,534
120 74.0 10,584
150 77.5 11,701
185 82.0 13,053
240 87.5 14,796
300 92.0 16,533

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.868 1.113 0.397 148 135 3.29 1.03
50 0.641 0.822 0.380 176 159 4.70 1.03
70 0.443 0.568 0.357 219 194 6.58 1.03
95 0.320 0.411 0.340 264 232 8.93 1.37
120 0.253 0.325 0.328 303 264 11.28 1.37
150 0.206 0.265 0.319 341 294 14.10 1.37
185 0.164 0.211 0.308 391 333 17.39 1.37
240 0.125 0.162 0.297 456 385 22.56 1.37
300 0.100 0.130 0.289 519 433 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information