N2XSEBY 3 x (35-300) mm² 12/20 kV

Cu / XLPE / CTS / PVC / STA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 56.5 4,322
50 59.0 4,883
70 63.0 5,836
95 66.5 6,905
120 70.0 7,907
150 74.0 9,096
185 77.5 10,488
240 84.5 13,454
300 89.5 15,722

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.524 0.668 0.395 190 174 5.01 1.03
50 0.387 0.494 0.379 226 205 7.15 1.03
70 0.268 0.342 0.357 280 250 10.01 1.03
95 0.193 0.247 0.341 338 298 13.59 1.37
120 0.153 0.196 0.328 387 338 17.16 1.37
150 0.124 0.159 0.318 437 378 21.45 1.37
185 0.0991 0.128 0.308 497 426 26.46 1.37
240 0.0754 0.098 0.296 580 488 34.32 1.37
300 0.0601 0.079 0.287 655 545 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information