N2XSEFGbY 3 x (25-300) mm² 6/10 kV

Cu / XLPE / CTS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 43.0 2,984
35 46.0 3,515
50 48.5 4,061
70 52.5 4,955
95 56.5 6,055
120 60.0 7,026
150 63.5 8,110
185 67.5 9,478
240 73.5 11,663
300 78.5 13,814

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 155 147 3.58 1.03
35 0.524 0.668 0.349 187 175 5.01 1.03
50 0.387 0.494 0.335 222 205 7.15 1.03
70 0.268 0.342 0.316 276 251 10.01 1.03
95 0.193 0.247 0.303 333 298 13.59 1.03
120 0.153 0.196 0.293 382 339 17.16 1.03
150 0.124 0.160 0.284 433 379 21.45 1.03
185 0.0991 0.128 0.277 493 426 26.46 1.37
240 0.0754 0.099 0.267 574 489 34.32 1.37
300 0.0601 0.080 0.261 650 546 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information